Redline
D.9
Contax R
A
B
C
D
E
F
G
X
Performance
Contax R
CTX + R16
Rated current (according to EN 60947-4-1)
250VAC (1 & 2 pole) / 400VAC (3 & 4 pole) A 16
Nominal thermal current (Ith) A 16
Number of pole 1 4
Contacts
NO 1 4
Changeover ("m" contacts) 1 4
NO + NC 1+1 / 2+2
Width (in 17.8mm DIN modules)
1P & 2P Mod. 1
3P & 4P Mod. 2
Coil specifi cations
Supply voltage : DC/AC ratio
(1)
0.5 / 1
Supply voltage range (in % of Un) % 85-110
Coil pick-up power 1P & 2P VA 3.4
3P & 4P VA 6.7
Coil power loss - AC 1P & 2P VA 1.8
3P & 4P VA 3.4
Coil power loss - DC 1P & 2P W 2.1
3P & 4P W 3.9
Maximum coil holding voltage time unlimited
Contact bounce time at closing
sec. <0.010
Operate and release time (bounce time incl.)
Pick-up time NO contact sec. < 0.040
(from 0 to Un) NC contact sec. < 0.020
Drop-out time NO contact sec. < 0.050
(from Un to 0) NC contact sec. < 0.050
Maximum peak current at closing
Single phase 250VAC cos
ϕ
= 0.95
A45
3-phase 400V~ cos
ϕ
= 0.65
A60
Maximum peak current at opening
Single phase 250VAC cos
ϕ
= 0.95
A75
3-phase 400V~ cos
ϕ
= 0.65
A60
Lifetime (in number of operations)
(2)
Electrical (in AC-1 - At full load) 3 x 10
5
Mechanical 2 x 10
6
Load specifi cations per phase
Maximum load AC-1 1P & 2P kW 3.0
3P & 4P kW 8.5
Maximum load AC-5b kW 1.8
Maximum load AC-7b kW 0.9
Maximum load AC-3 250VAC kW 1.5
400VAC kW 2.2
Minimum load (under 5V) W 2
Short-circuit fuse protection A 20
Maximum lamp load (10³ operations/h)
Incandesc. & halogen (40 to 200 W lamps) W 1,800
Fluorescence, compensated (cos
ϕ
= 0.9)
Serial compensation VA 1,800
Parallel compensation VA 500
Fluorescence, non compensated (cos
ϕ
= 0.5)
VA 900
General specifi cations
Auxiliary contact add-on (PLS / CTX R) yes
Need for spacer no
DIN rail mounting yes
2-position DIN rail lock yes
Front handle for manual operation yes
Permanent ON/OFF no
Indicator of contact position yes
Clamping terminals yes
Unlosable screws yes
Sealable terminals (coil and load) yes
Cable cross section (Ø min/max) Coil mm² 1.5 / 10
Load mm² 1.5 / 10
Maximum torque on terminals Nm 1
Ambient temperature at installation point (min./max.) °C -20 / +45
(1) DC supply voltage = AC supply voltage x DC/AC ratio, except for 8VAC and 115VAC (48VDC)
(2) 1 cycle = 2 operations per pole (closing + opening)